Rated motor current | 5-630 А |
PC and Android app | Yes |
Communication protocol | Modbus RTU |
Number of protections | 10 |
Connecting external current transformers | Yes |
Mass | no more than 0,34 kg |
Overall dimensions, mm | 110 x 96 x 88,3 |
Indication | LCD display |
Brand | Novatek |
UBZ-304 is designed for the protection of asynchronous electric motors with power from 2.5 to 315 kW when using external standard current transformers with an output current of 5 A.
UBZ-304 can operate in networks with both isolated and solidly grounded neutrals.
The device is panel-mounted.
UBZ provides continuous monitoring of network voltage parameters, actual values of phase (line) currents of three-phase electrical equipment 380 V 50 Hz, and checking the insulation resistance of electric motors.
UBZ-304 provides protection for motors in the case of:
– Poor network voltage (unacceptable voltage fluctuations, phase loss, phase sequencing and sticking violations, asymmetry of phase/line voltages, decrease in network frequency below the set value and/or increase in network frequency above the set value);
– Mechanical overloads (symmetrical increase in phase/line currents);
– Exceeding the reverse sequence current threshold;
– Asymmetry of phase currents without overload, related to insulation damage inside the motor and/or power cable (comparison of the current asymmetry coefficient of the reverse sequence with the voltage asymmetry coefficient of the reverse sequence);
– Disappearance of torque on the motor shaft (“dry running” – for pumps) – protection against minimum starting and/or operating current;
– Extended motor start or rotor blocking;
– Unacceptably low insulation resistance between the stator and motor body (pre-check before start-up);
– Stator winding “earth” fault during operation – protection against “earth” leakage currents;
– Thermal overload of the motor;
– Winding overheating (determined by winding temperature when using built-in temperature sensors or casing temperature when using external temperature sensors).